ba.gif (8919 bytes)
home

PLANT AND SECTION VIEW OF RESINTECH SEPTIC TANK
(MODEL - RST5)

NB: Septic Tank Outlet Discharge Pipe to Manhole Shall Be According to Local Authority Approval

NB : For Cases of Shallow Type of Drain Using of Pump Sump Required

 

SECTION A - A


PLAN [SEPTIC TANK RST 5]

(Lulus Olih Jpp Pada 06/11/1998)
Design Parameters RST 5
Separation Chamber Volume [Litres] 5,083
Filteration Chamber Volume [Litres] 950
Height [MM] 1,900
Width Diameter [MM] 1,840
Length [M] 2,550
Weight [KG] 268
Thickness [MM] 8-10
Inlet & Outlet Pipe Diameter [MM] 150
Ventilation Pipe Diameter [MM] 25
Hydraulic Retention Time [[HR.] 28
Filter Volume [Litres] 215
Hydraulic Loading M3/M2/D 1.85
Organic Loading Kg.Bod/D 0.25
Daily Load Kg.Bod/D 1.4
Filter Media PVC Rings
Filter Surface To Volume Ratio M2/M3 >50
Population Equivalent 22

Efficiency of Treatment

The RESINTECH Individual Septic Tanks Model RST 5 are designed to be used for Residential and Commercial Buildings with a population equivalent of 22 people.

The Standard to satisfy is the Malaysia Environmental Quality Regulation, 1979 Standard B.

STANDARD DESIGN CALCULATION

Design Data :
System : Resintech Individual Septic Tank Model RST 5
Type of Sewage : Residential / Commercial
Design Flow : 5.6m3/day
Population Equivalent : 22pc

EFFICIENCY OF SUSPENDED SOLID REMOVAL

Resintech Individual Septic Tank Model RST 5 80% of the Suspended Solids are considered to be removed in the sedimentation process.

Design Influent x (100 -80) %
300 mg/l x (100 - 80) %
= 60 mg/l.

EFFICIENCY OF BOD REMOVAL
Resintech Individual Septic Tanks Model RST 5 60% of the BOD are considered to be removed in the Anaerobic System.

Design Influent x (100 - 60) %
250 mg/l x (100 - 60) %
= 100 mg/l.

Further in the Filteration Chamber, BOD is further reduced with an efficiency of 75%.

Final BOD = 100 mg/l x (100 - 75) % =25 mg/l.

ORGANIC LOADING (OLR)

OLR

Average BOD x Design Flow (kg/m3.d)
Volume of Septic Tank

=

0.25 kg/m3 x 5.6m3/d
5.63m3/d

=

0.25kg/m3.d.

HYDRAULIC RETENTION TIME (HRT)

HRT = Chamber volume / design flow
= 5.63m3/5.6 m3/d
=1.01 day > 24 hours (good for settling of organics)

SLUDGE GENERATION

The design sludge production rate = 0.04 m3/pe/yr. Assuming the settled sludge can accommodate 40% of the chamber.

Estimated desludging period =

Volume of sludge accumulated
Sludge produced

=

0.4 x 5.63m3
0.04 x 25m3/yr.

=

2.25years